Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Preslab  

Permit Number - TC-RES-1124-06868

Inspection Description - COT - RSBU - Preslab  

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
03/17/2025 COT - RSBU - Preslab   Re-inspection required 15 March 25
1. UFER needs to extend above earth and ground connection needs be accessible after concrete is poured. At the current situation it will be covered by concrete.
2. Rebar must also separated 3" from earth.
03/19/2025 COT - RSBU - Preslab   Passed Ok to place concrete,in slab area. Ensure slab area is termite treated.