Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Plumbing Final
Permit Number - TC-RES-1124-06768
Inspection Description - COT - RSPL - Plumbing Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2025 | COT - RSPL - Plumbing Final | Re-inspection required | 6-10-25: not ready | |
| 07/08/2025 | COT - RSPL - Plumbing Final | Not Ready | 7-8-25: not ready-contractor will reschedule | |
| COT - RSPL - Plumbing Final | Re-inspection required | 7-15-25: missing hammer arrestor at dishwasher, furnace not connected, hallway bathroom fan not working, remove all covers from smoke detectors, bedroom 1 is missing a receptacle,master bedroom is 2 receptacles, and hallway is missing 1 receptacle, panel is missing an updated schedule-water heater not marked, plans call for an a/c 40 amp breaker and you installed a split unit. Either Provide a revision reflecting this or install as per approved plans, pressure relieve valve must be pvc or cpvc, missing electrical cover at laundry room, thermostat must be installed no higher than 48" o.c., exterior receptacles must be weather resistant, insulate hose bibs with r-3 and tape using 10 mil tape. STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE NOTED. | ||
| 09/12/2025 | COT - RSPL - Plumbing Final | Re-inspection required |