Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
Permit Number - TC-RES-1124-06761
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2025 | COT - RSEL - Electrical Final | Re-inspection required | 5/20/25 1. Kitchen requires 2 GFCI circuits. 2. Loose outlets in kitchen and dining room. 3. Water hammer arrestors needed at washer and fridge water inlet. 4. Missing receptacles in bedrooms. 5. All exterior outlets must be WR rated. 6. Thermostat too high, 48" max. |
|
| 06/06/2025 | COT - RSEL - Electrical Final | Not Ready | No access for inspection |