Inspection History Details
Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
Permit Number - TC-RES-1124-06761
Inspection Description - RSBU - Building Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2025 | RSBU - Building Final | Re-inspection required | 5/20/25 1. Kitchen requires 2 GFCI circuits. 2. Loose outlets in kitchen and dining room. 3. Water hammer arrestors needed at washer and fridge water inlet. 4. Missing receptacles in bedrooms. 5. All exterior outlets must be WR rated. 6. Thermostat too high, 48" max. |
|
| 06/06/2025 | RSBU - Building Final | Not Ready | no access for inspection | |
| 06/06/2025 | RSBU - Building Final | Not Ready | No access for inspection | |
| 06/09/2025 | RSBU - Building Final | Re-inspection required | ||
| 09/11/2025 | RSBU - Building Final | Passed |