Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Partial Pass | 7/10/25 Partial pass; 1.Seal all penetrations at 10ft and top plate. 2. Island Electrical needs to be pulled and must be UF rated. 3. Protect piping in laundry with bang plates. Top plates must have boca plates that extend minimum 2" below. |
|
| 07/28/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | 7/28/2025 missing smoke detectors at bedrooms and outside of bedrooms. Secure pex lines every 4' vertically. Receptacle in kitchen areas exceeding spacing. 2' from range every 4´ after. | |
| 08/06/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 8.6.25 approved |