Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 02/17/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
2-17-26: add anchor bolts 32" o.c. Maximum, change headers to 2x8's, add nails to exterior sheathing along edges between 3/8" -1/2" maximum & add nails edges/in the field per plans, add top plates at south and north walls, plans call for 2x6's at 16" o.c.- either install per plans Or submit a revision to the city for review for 2x6's at 24" o.c...STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE ADDED. |
| 02/23/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Partial Pass |
Partial pass. Corrections were made. No additional items needed. Pending interior framing. 2/23/2026 |