Inspection Status: Passed

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Permit Number - TC-RES-1124-06640

Inspection Description - COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Inspection Status - Passed

Date Description Inspector Results Comments
01/13/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed 1.13.26
Revisions made as well as corrections. Only remaining item is electrical underground, which sits currently at 6 inches. Fix needed for that.
09/19/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 1-Main beams are not per approved plans.
2-H2.5s are not installed per approved plans.
3-2x2 steel runners are not shown on approved plans.
4-Metal roofing is not shown on approved plans.
5-Work is covered.
6-Open electrical outlets for inspection.
Build per plan, or obtain revision to have changes approved.