Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
Permit Number - TC-RES-1124-06349
Inspection Description - COT - RSME - Mechanical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2025 | COT - RSME - Mechanical Final | Re-inspection required | 7/2/25 1. Unit needs to be leveled for proper operation 2. Drain pipe needs to be painted to prevent cracking 3. Label the heater kit used; 4. Maximum Overcurrent protection is 30 amps you have 35 amp fuses; also could not find breaker for Unit. |