Permit: TC-RES-1124-06349

Parcel: 117071000


Addresses:

537 S 4TH AV

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical FinalĀ 

Date Description Inspector Results Comments
07/02/2025 COT - RSME - Mechanical FinalĀ  Re-inspection required 7/2/25
1. Unit needs to be leveled for proper operation
2. Drain pipe needs to be painted to prevent cracking
3. Label the heater kit used;
4. Maximum Overcurrent protection is 30 amps you have 35 amp fuses; also could not find breaker for Unit.