Inspection History Details
Inspection Status: Not Ready
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2024 | RSBU - Building Final | Not Ready | 7/15/24: roof nailing passed ok to dry-in | |
| 08/21/2024 | RSBU - Building Final | Re-inspection required | 7/15/24: roof nailing passed ok to dry-in 8/21/24: Attic light and receptacle not made up, A/C condenser must have refrigerant lines UV protected, lock out caps required at condenser, thermostat wire must be protected from elements, A/C disconnect missing cover plate, bedroom closet missing light fixture, air handler must have NM cable secured 12" from box, wiring at disconnect box for air handler is a code violation. |
|
| 08/22/2024 | RSBU - Building Final | Passed | all items completed |