Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-RES-1123-09704

Parcel: 129053290


Addresses:

2106 E 18TH ST

Inspection Status: Passed

Inspection History: COT - RSPL - Plumbing Final 

Date Description Inspector Results Comments
04/01/2025 COT - RSPL - Plumbing Final  Passed
12/06/2024 COT - RSPL - Plumbing Final  Re-inspection required 12/6/24: anti-tip required at range, GFCI required at bathroom within 36" of basin, caulk water closet, properly insulate water lines in closet and seal penetration, exhaust fan missing in bathroom, sub panel not permitted in closet, no power at smoke alarms, revision required for mechanical changes, no roof access. kitchen receptacles must be GFCI.