Permit: TC-RES-1123-09497

Parcel: 114570980


Addresses:

2487 N WYCHWOOD CT

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
07/25/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Have engineer of record evaluate and verify the following issues:
1-Beams are not connected per plans. 2-trusses are not protected from rotation at ends. 3-Verify span of 2 by 6 valley framing. 4-Evaluate split at bearing end of gable. 5-evaluate bearing condition at pony walls on roof. 6-North glu-lam is upside down.
08/13/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Partial Pass valley framing is good; ok to cover gable wall.

1-Remove and Renault all shiners. 2-Install blocking at top of pony walls per details on plans. 3-Nail shear at 6” O. C. max at all edges. 4-Complete blocking and shear at non-bearing gable wall per plans.
08/22/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Partial Pass 1-Nail blocking at gable wall below truss at 6” O. C. 2-Shear truss per engineered drawings. reschedule with intermediate. ok to proceed elsewhere.
09/13/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed