Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | Have engineer of record evaluate and verify the following issues: 1-Beams are not connected per plans. 2-trusses are not protected from rotation at ends. 3-Verify span of 2 by 6 valley framing. 4-Evaluate split at bearing end of gable. 5-evaluate bearing condition at pony walls on roof. 6-North glu-lam is upside down. |
|
| 08/13/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Partial Pass | valley framing is good; ok to cover gable wall. 1-Remove and Renault all shiners. 2-Install blocking at top of pony walls per details on plans. 3-Nail shear at 6” O. C. max at all edges. 4-Complete blocking and shear at non-bearing gable wall per plans. |
|
| 08/22/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Partial Pass | 1-Nail blocking at gable wall below truss at 6” O. C. 2-Shear truss per engineered drawings. reschedule with intermediate. ok to proceed elsewhere. | |
| 09/13/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed |