Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-RES-1123-09343
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Not Ready
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Not Ready | 1-Rafters are not bird’s-mouthed as required by IRCR802.6. 2-Hardware installation ic incomplete. 3-Ledger bolts at front porch are not per approved plans. 4-Rear ledgers are not installed per approved plans. 5-Foundation bolts are not installed per IRC R403.1.6. Inspection stopped; walk for compliance with Code/Plans before rescheduling. Future inspections may produce additional corrections and/or fees. |
|
| 05/06/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Not Ready | No corrections have been made since last visit; met builder and explained corrections as well as pointed out that existing rafters are over spanned. | |
| 05/20/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed |