Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
Permit Number - TC-RES-1122-01119
Inspection Description - COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | Plans call for a total of 7 columns. 6 are in the field. Add blocking so that every hole is nailed for the hardware. Add hardware to both ends of rafters. Provide detail on box headers at both ends for point of attachments. Add nails that are missing East end hangers. Revise set of plans to match what’s being installed in the field. Electrical lines need to be in place along with the fan boxes prior to intermediate inspection. 8/7/2025 | |
| 08/12/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 8-12-25: electrical intermediate inspection approved. See framing notes. |