Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof Nailing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2025 | COT - RSBU - Roof Nailing | Re-inspection required | Plans call for a total of 7 columns. 6 are in the field. Add blocking so that every hole is nailed for the hardware. Add hardware to both ends of rafters. Provide detail on box headers at both ends for point of attachments. Add nails that are missing East end hangers. Revise set of plans to match what’s being installed in the field. Electrical lines need to be in place along with the fan boxes prior to intermediate inspection. 8/7/2025 | |
| 08/12/2025 | COT - RSBU - Roof Nailing | Re-inspection required | 8-12-25: add nails at columns and along edges at face of sheathing 6" o.c..Install remaining missing sheathing at soffits and submit the required revision reflecting the 6 columns. | |
| 09/26/2025 | COT - RSBU - Roof Nailing | Passed | 9/26/25 Pass |