Inspection Status: Re-inspection required

Inspection History: RSEL - Electrical Progress

Date Description Inspector Results Comments
04/28/2026 RSEL - Electrical Progress Re-inspection required Provide missing smoke detectors at all bedrooms and out side of bedroom west end. All should be hard wired together. Provide receptacles at kitchen counter tops 2' from sink both ends. Move over receptacle for dishwasher to be accessible. Provide two receptacles in hallway. Provide exterior receptacles one at front the other in back. Replace pancake boxes that have open slots. Provide ground screws at all metal boxes. Provide pan for water heater along with t&p line. Remove tape from vent and provide 3 screws. One on each side. Call in this inspection prior to final to verify before coverage. 4/28/2026
05/12/2026 RSEL - Electrical Progress Passed 05/12/2026
All corrections add to prior inspection. Verified added rated pipe to pressure and temperature relief discharge line at water heater and carbon monoxide detector.