Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - BULD - SWG Clearance
Permit Number - TC-RES-1024-06288
Inspection Description - COT - BULD - SWG Clearance
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2024 | COT - BULD - SWG Clearance | Re-inspection required | 11-1-24, customer was utilizing a 30 psi gauge. Per city code, customer must use a 15 gauge and have galvanized gas pipe tested at 15psi for minimum of 10 minutes. | |
11/05/2024 | COT - BULD - SWG Clearance | Passed | 11-5-24, verified gauge at 15psi. Clearance for connection issued to Southwest Gas Co. |