Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2024 | COT - RSEL - Electrical Final | Re-inspection required | Gas and water lines need to be bonded. 11/29/2024 | |
| 12/03/2024 | COT - RSEL - Electrical Final | Re-inspection required | Gas and water lines need to be bonded. 11/29/20242 12/3/24: bonding wire not proper size. Please refer to Table E3603.4 in the 2018 IRC. Supports for panel and riser must be weather treated. |
|
| 12/04/2024 | COT - RSEL - Electrical Final | Passed |