Inspection Status: Re-inspection required

Inspection History: COT - RSOL - Electrical Final Solar Project

Date Description Inspector Results Comments
02/13/2025 COT - RSOL - Electrical Final Solar Project Re-inspection required 13 FEB 25
1. Tesla Powerwall is not installed per plan, sitting about 5" from ground, plan calls for 48 inches.
2. Wire length too short from MSP to DG disconnect should be min of 15.5 ft.
04/04/2025 COT - RSOL - Electrical Final Solar Project Passed