Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Permit Number - TC-RES-1024-06037

Inspection Description - RSBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
02/13/2025 RSBU - Building Final  Re-inspection required 13 FEB 25
1. Tesla Powerwall is not installed per plan, sitting about 5" from ground, plan calls for 48 inches.
2. Wire length too short from MSP to DG disconnect should be min of 15.5 ft.