Permit: TC-RES-1024-05932

Parcel: 120030470


Addresses:

1131 W COLUMBIA ST

Inspection Status: Re-inspection required

Inspection History: BULD - Electrical Clearance

Date Description Inspector Results Comments
02/28/2025 BULD - Electrical Clearance Re-inspection required Failed - 1. New all-in-one service panel is mounted too high and must be lowered 2. Existing service riser and service condutors do not comply and must be changed with new weather head 3. Grounding and bonding
04/09/2025 BULD - Electrical Clearance Partial Pass TEP called at 12:47 for INCR clearance
07/17/2025 BULD - Electrical Clearance Passed