Inspection History Details
Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2024 | RSBU - Building Final | Re-inspection required | 3/14/24: Caulking missing at toilets, water hammer arrestor missing at (fridge,dishwasher and laundry), anti-tip missing at range, receptacle under sink must be GFCI, laundry room receptacles must be GFCI, insulation needs at hot water line at water heater, properly insulate hose bibs and wrap for UV protection, Arc-fault breaker's missing at multiple locations. No ladder for Mechanical final. | |
| 03/26/2024 | RSBU - Building Final | Re-inspection required | 3/14/24: Caulking missing at toilets, water hammer arrestor missing at (fridge,dishwasher and laundry), anti-tip missing at range, receptacle under sink must be GFCI, laundry room receptacles must be GFCI, insulation needs at hot water line at water heater, properly insulate hose bibs and wrap for UV protection, Arc-fault breaker's missing at multiple locations. Sediment trap missing at water heater. No ladder for Mechanical final. 3/26/24: corrections not made per previous notes, A/C unit condensate drainage and gas line not installed, fuses are not installed at A/C unit |
|
| 03/28/2024 | RSBU - Building Final | Passed |