Permit: TC-RES-1023-08577

Parcel: 140270040

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
01/04/2024 COT - RSME - Mechanical Final  Re-inspection required 1/4/23: Mini split, breaker being over amped max 15amp, mini split must be properly fastened to base, proper underground electrical conduit must be installed, condensate must be 6” above grade, refrigerant lines must be coated for up protection, underground electrical must be at proper burial.
01/25/2024 COT - RSME - Mechanical Final  Passed 1/4/23: Mini split, breaker being over amped max 15amp, mini split must be properly fastened to base, proper underground electrical conduit must be installed, condensate must be 6” above grade, refrigerant lines must be coated for up protection, underground electrical must be at proper burial.
1/25/24: corrections made