Parcel: 117030020


Addresses:

835 N 1ST AV


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Firewall/Fire Barrier/Firestop 

Permit Number - TC-RES-1023-08449

Inspection Description - COT - RSBU - Firewall/Fire Barrier/Firestop 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
11/13/2025 COT - RSBU - Firewall/Fire Barrier/Firestop  Re-inspection required 11/13/25: Inspection were never called in during time of construction, please provide proper documentation of 1-hour fire rated assembly, electrical not per plan (missing circuits throughout, multiple circuits tied together), receptacle spacing at kitchen countertop and wall space none code compliant. Exhaust fan missing at upstairs unit bathroom, piping at bathroom vanity none code compliant. Properly secure all exterior raceways at main panel, insulation required at exterior domestic supply lines, light fixtures at basement must be rated for the application, roof access required for final, laundry/storage room has been demolished (revision required), windows must be tested to open to meet egress requirements, smoke alarms must be 3' from air supplies and fan fixtures, water hammer arrestor required at refrigerator, hot water heaters were not inspected, ac units were not inspected. Letters from licensed contractor required prior to final for plumbing work, electrical work, mechanical work, framing work completed prior to the completion of any inspections.