Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Date Description Inspector Results Comments
09/29/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 9/29/26:,Per IECC C404.4 Insulation on 3/4 pex lines is required. Add R3 insulation to 3/4" pex lines in attic and at walls, fire foam penetrations at living room top plates including DWV, add fire foam to penetrations at master shower and at north wall of master bedroom, a support strap to pex line for hose bib within 4' is required, add additional fire foam around penetration at water heater top plate & R3 insulation is required on hot copper line of water heater. Make corrections & reschedule an inspection. Home not ready to drywall.
10/01/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed 10/1/26: intermediates approved. Okay to drywall.