Permit: TC-RES-0926-05221

Parcel: 141163920


Addresses:

9591 E CALDWELL DR

Inspection Status: Re-inspection required

Inspection History: COT - RSPL - Plumbing Final 

Date Description Inspector Results Comments
09/22/2026 COT - RSPL - Plumbing Final  Re-inspection required 9/22/26: support booster pump at water heater, insulation required on hot water side of water heater, flexible gas connector for pressure relief valve not allowed, all hot pex lines 3/4" must be properly supported ( cannot lie on trusses) and require insulation, add insulation to hose bib at front yard and seal penetration at exterior wall and provide a ladder for attic access. Reschedule inspection when corrections are made.
09/28/2026 COT - RSPL - Plumbing Final  Re-inspection required 9/28/26: no answer at pre call or at residence. Rang door bell a few times, waited a few minutes and left.
Note: a water heater pan is required. I forgot to add to previous notes.
09/29/2026 COT - RSPL - Plumbing Final  Partial Pass 9/29/26: partial pass pending section of R3 insulation on hot copper line of water heater. Provide a photo so that I may close out permit.
10/01/2026 COT - RSPL - Plumbing Final  Passed 10/1/26: plumbing final approved.