Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-RES-0926-05185

Parcel: 118033060


Addresses:

2160 W SAN JUAN TR

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Excavation/Rebar/Zoning 

Date Description Inspector Results Comments
11/02/2026 COT - RSBU - Excavation/Rebar/Zoning  Re-inspection required 11/2/26: 95% compaction at porch pad not met due to wet conditions, install #4 rebar at 4' lengths on chairs at corners-see plans for required locations, 1 1/2" clearance from DWV & forms is required. Schedule inspection when footers & vapor barrier are dry of rain water.
11/06/2026 COT - RSBU - Excavation/Rebar/Zoning  Passed 11/6/26: excavation/reinforcement & pre slab approved. Okay for concrete placement.