Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Preslab
| Date |
Description |
Inspector |
Results |
Comments |
| 11/02/2026 |
COT - RSBU - Preslab |
|
Re-inspection required |
11/2/26: 95% compaction at porch pad not met due to wet conditions, install #4 rebar at 4' lengths on chairs at corners-see plans for required locations, 1 1/2" clearance from DWV & forms is required. Schedule inspection when footers & vapor barrier are dry of rain water. |
| 11/06/2026 |
COT - RSBU - Preslab |
|
Passed |
11/6/26: excavation/reinforcement & pre slab approved. Okay for concrete placement. |