Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | 8.1.25 Brace 4 slot electrical boxes DWV not under test Circuit count does not match plans STOPPED INSPECTION MORE ITEMS MAY BE PRESENT |
|
| 08/12/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | 8.12.2025 Partial corrections made, DWV still not under test, electrical panel A has 15 circuits but plan shows 22, PEX line needs to be 12” from recessed light or blocked, seal exterior penetrations, missing exhaust fan in bathroom, missing some nail plates in ABS in bathroom within 1.5” of stud face, secure ABS at ceiling in bathroom, secure condensate line, secure electrical line set in study. Water heater room required 18” of copper line from main and up to the two PEX lines. Existing house Romex line cannot be in masonry walls, PEX in crawl space needs insulated. Storage area approved. |
|
| 08/15/2025 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 8.15.2025 Corrections made, okay to proceed. |