Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical FinalĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 01/29/2025 |
COT - RSME - Mechanical FinalĀ |
|
Re-inspection required |
No insulation in ductwork on roof, please determine heat strips if installed, blocking required on whip and condensate, roof jacks required on roof penetrations, 30 amp max fuse for basic unit, water heater is 40 amp max, paint/seal all spiral duct after insulation is verified, elbow down on condensate required, thermostat is to high on wall |