Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
Permit Number - TC-RES-0924-05629
Inspection Description - COT - RSME - Mechanical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2025 | COT - RSME - Mechanical Final | Re-inspection required | No insulation in ductwork on roof, please determine heat strips if installed, blocking required on whip and condensate, roof jacks required on roof penetrations, 30 amp max fuse for basic unit, water heater is 40 amp max, paint/seal all spiral duct after insulation is verified, elbow down on condensate required, thermostat is to high on wall |