Inspection Status: Re-inspection required
Inspection History: BULD - Electrical Clearance
Permit Number - TC-RES-0924-05469
Inspection Description - BULD - Electrical Clearance
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/17/2024 | BULD - Electrical Clearance | Re-inspection required | 1-Panel is rated for 200 amps; approved plans specify 250 amps. 2-Approved plans do not show second service. 3- Neither service is grounded. 4- Both services have unused openings that need to be closed. 5-Bare wires are extending from wall. 6-No access for inspection inside. | |
10/24/2024 | BULD - Electrical Clearance | Passed | ||
10/29/2024 | BULD - Electrical Clearance | Passed | 10/28/24: RECN TEP clearance |