Permit: TC-RES-0924-05271

Parcel: 131043740


Addresses:

4834 E 28TH ST

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
04/15/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 15 April 25
1. Laundry standpipe is too short, needs to be minimum 18" from weir of the pipe.
2. Pipe trap arm in laundry is too short, needs to be 2x pipe diameter.
3. No plans on site.
4. Combination CO/smoke detector needed.
04/18/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed