Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 10/30/24: no access to site. | |
| 11/01/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 10/30/24: no access to site. 11/1/24: Anchor bolt spacing shall be no more than 32" o.c, anchor bolts required within 12" of edge of sill plate, H2.5 required throughout at trusses, fire wall not framed per plan, 2x blocking required per detail S2.2 at trusses, king/trimmer studs not per schedule, straps required at all openings at headers, nailing at roof not per schedule, shims required at at 2x6 at bearing walls to make full contact with double top plate. 11/13 corrections have been made. pass |
|
| COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 11/13 corrections have been made. pass |