Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Date Description Inspector Results Comments
10/30/2024 COT - RSBU - Roof Nailing  Re-inspection required 10/30/24: no access to site.
11/01/2024 COT - RSBU - Roof Nailing  Re-inspection required 10/30/24: no access to site.
11/1/24: Anchor bolt spacing shall be no more than 32" o.c, anchor bolts required within 12" of edge of sill plate, H2.5 required throughout at trusses, fire wall not framed per plan, 2x blocking required per detail S2.2 at trusses, king/trimmer studs not per schedule, straps required at all openings at headers, nailing at roof not per schedule, shims required at at 2x6 at bearing walls to make full contact with double top plate.
COT - RSBU - Roof Nailing  Passed 11/13 corrections have been made. pass