Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 1. Missing 4x4 column on east wall; plan also calls for a 6x10 beam and currently installed is a 4x9 Glulam. 2. Detail 4/S2.0 is calling for treated sill plate at gable ends with Hilton pins at 32" oc. 3. Same thing with detail 7/S2.0 *****please update plans to reflect current conditions.****** |
|
| 10/30/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Partial Pass | 10/30/26 ****Okay to proceed at own risk, pending revisions to above findings.**** |