Permit: TC-RES-0825-03979

Parcel: 141145720

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
01/15/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 01/15/2026
At ramada could not verify anchor bolts at all columns due to covered up by osb. Add H2.5s to 2x6 rafter ends to beam at ramada. In office add anchors bolts within 12" and 4" min of sill plate edges as marked. Outside wall shearing add nails not more than 3/8" from edge as marked.
01/22/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 1.22.26
Changes approved