Permit: TC-RES-0825-03974

Parcel: 136202440


Addresses:

2602 S CAMINO SECO

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Date Description Inspector Results Comments
03/02/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 3/2/26: will recall once issues are addressed and all missing components of permit are completed.
08/24/2026 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 3/2/26: will recall once issues are addressed and all missing components of permit are completed.
8/24/26: Properly secure NM cable 8" from box, install metallic boxes at block wall, nm at block wall must be protected, smoke detector shall not be more than 12" from ceiling, smoke detectors shall be interconnected, fire foam all penetrations through top plate, laundry room pending, receptacle spacing shall meet code requirements, AFCI required at branch circuits. Bubble covers required at exterior receptacles, receptacle pending at peninsula.
11/04/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Not Ready Not ready; remove insulation to allow for framing/intermediate inspections.
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Not Ready 1-Studor vent needs to be accessible.
2-Nail plates missing at plumbing throughout.
3-Studs are over-notched at laundry wall.
4-Holes in bedroom are drilled less than 2" from bottom.
5- Install ductwork per manufacurer's instructions.
6-Complete framing.
Nor ready. Inspection stopped. If inspection does not pass next time, a re-inspection fee will be assessed.