Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Date Description Inspector Results Comments
08/28/2025 RSBU - Building Final  Re-inspection required 1. Sub panel is missing dead front, and also need to separate ground and neutrals.
2. Main panel deadfront has many openings that must be covered.
3. Entry threshold is too high, should be 1/2" or less.
4. Outlet in kitchen counter is blocked by the top corner of oven.
5. Plan is showing a ramp leading up to front door.
08/29/2025 RSBU - Building Final  Re-inspection required 8/29/25: Construction fencing in place, broken concrete present, no accessible path per inclusive home design requirements.
08/29/2025 RSBU - Building Final  Re-inspection required 8-29-25: per previous notes, the ramp is missing-see plans for details. Install knockout underneath main panel.
09/02/2025 RSBU - Building Final  Passed 9/2/25: Construction fencing in place, broken concrete present, no accessible path per inclusive home design requirements.