Parcel: 107110090

Inspection Status: Re-inspection required

Inspection History: COT - LCEL - Electrical Final 

Permit Number - TC-RES-0824-04904

Inspection Description - COT - LCEL - Electrical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/09/2024 COT - LCEL - Electrical Final  Re-inspection required 9/9/24: electrical wire needs to be in conduit running from main panel. Hole in bottom of main panel needs to be plugged. Missing dead front at main panel. Gas and water lines need to be bonded.