Inspection History Details
Inspection Status: Requested
Inspection History: COT - RSEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COT - RSEL - Electrical Final | Requested | |||
| 09/11/2025 | COT - RSEL - Electrical Final | Not Ready | no access for inspection | |
| 09/12/2025 | COT - RSEL - Electrical Final | Re-inspection required | 9.12.25 Water hammer arresters missing at washer box in laundry and at hot water line at sink/dishwasher Outlet receptacles are missing and not per plan in the 2 east bedrooms Panel schedule missing Incorporate arc fault breakers as per plans and code requirement |
|
| 12/24/2025 | COT - RSEL - Electrical Final | Re-inspection required (with fee) | 12.24.25 Arc faults are requires per code and plan. Contractor expressed that the old wiring doesn't support arc faults however submitted plans call for new receptacles and arc faults. Work must abide by plans and code |