Inspection Status: Partial Pass
Inspection History: COT - RSPL - Gas Pressure Test
| Date |
Description |
Inspector |
Results |
Comments |
| 03/19/2026 |
COT - RSPL - Gas Pressure Test |
|
Partial Pass |
Underground |
| 04/02/2026 |
COT - RSPL - Gas Pressure Test |
|
Passed |
|
| 04/15/2025 |
COT - RSPL - Gas Pressure Test |
|
Not Ready |
|
| 05/05/2025 |
COT - RSPL - Gas Pressure Test |
|
Not Ready |
1-No test on piping. 2- Tracer wire missing from plastic piping underground. |
| 05/07/2025 |
COT - RSPL - Gas Pressure Test |
|
Partial Pass |
1-Test gauge is incorrect size; it does not show 1/10 of pound increments per Code. 2-Dryer has been eliminated. 3-Tracer wire for underground gas piping is blue; it needs to be yellow. 4- Tankless water heater had not been roughed in per approved plans. 5-Gas piping for rooftop unit terminates in attic with shut-off valve more than three feet from location and inaccessible for rooftop; cannot run flex line through roof sheeting, roof jack, etc. 6-There is no gas piping shown on approved plans; installed 3/4” main seems inadequate for appliances intended size and location. obtain approved revision showing size, type, and location of all tended gas piping. |