Inspection Status: Not Ready
Inspection History: COT - RSEL - Electrical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 01/18/2024 |
COT - RSEL - Electrical Final |
|
Not Ready |
Ground rides not installed properly and main feeders are not connected. Please verify, panel, neutral, and ground buses are separated properly. |
| 01/19/2024 |
COT - RSEL - Electrical Final |
|
Re-inspection required |
1/19/24: refrigerant lock caps missing, feeding wires need to be properly identified at main panel and sub panel, ground and neutral buses must be separated properly. Labeling on sub-panel missing, panel cover needs labeling. ok to backfill trench. |
| 01/24/2024 |
COT - RSEL - Electrical Final |
|
Passed |
Corrections were made. 1/24/2024 |