Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Re-inspection required

Inspection History: COT - RSPL - Plumbing Final 

Date Description Inspector Results Comments
08/21/2026 COT - RSPL - Plumbing Final  Re-inspection required 8.21.26
1. Kitchen counter receptacles have to be GFCI protected, also ,missing receptacle at 21" counter between range and fridge. Improper receptacle spacing at counter perpendicular to sink, at no point on the counter should a receptacle be more than 24" away.
2. Install anti bracket for range
3. Dishwasher not anchored down, install water hammer arrestor for dishwasher hot supply.
4. Seal missing knockout at main service panel bottom.
5. Water needs to be on so fixtures and plumbing can be tested
6. HVAC not working, also provide ladder to inspect unit
7. Address numbers missing, please add numbers minimum 4" in height and .5" width contrasting with background(black should work with this house).
8. Outdoor lighting needs to be fully shielded or full cut off per Pima Country ordinance.
9. No plans on site. More items maybe added at a later inspection due to missing plans.
09/01/2026 COT - RSPL - Plumbing Final  Not Ready Not ready, site locked and wrong lockbox code provided.
09/03/2026 COT - RSPL - Plumbing Final  Not Ready
09/04/2026 COT - RSPL - Plumbing Final  Re-inspection required
09/09/2025 COT - RSPL - Plumbing Final  Canceled Canceled per contractor. 9/9/2025
09/09/2026 COT - RSPL - Plumbing Final  Re-inspection required 9/9/26 need ladder for attic access, water should be turned on to test fixtures, GFCI outlet to right of range not functional, receptacle is loose, water heater not installed correctly, needs drip leg. New code 7918
09/16/2026 COT - RSPL - Plumbing Final  Not Ready 9/16/2026 Provide address per previous notes. Receptacle to the right of range shall be GFCI protected. Receptacle at countertop east wall shall be GFCI protected. Provide high water loop at dishwasher. Ensure dishwasher is secured in place. Water heater drip led shall be facing down. Pressure relief valve shall be out of CPVC or copper. Coat exterior plastic pipes on roof. Add flashing to 3” vent line on roof. Provide WR gfci protected receptacle on roof. Mark (X) to the column and row to indicate selected option installed on unit label. Raise gas exhaust per code section r303.5.1.
09/23/2026 COT - RSPL - Plumbing Final  Passed 09/23/2026
Verified all corrections made to prior inspections.