Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
|
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
1/3/24: approved plans and permit not on site. chard lumber cannot be used. Over notched lumber needs to be replaced or sistered together. |
| 01/04/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Not Ready |
1/4/2023. Bedroom windows not per code. Add fire blocking at 8' in new addition. Double French door. 5' opening requires double king studs with straps going from header to studs. Provide engineer fix on broken truss in front entry. Plans show trusses going through front entry porch. Provide revision as built plans. Revise the smoke damage on the east end of kitchen area. |
| 05/28/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|
| 05/28/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|