Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Excavation/Rebar/Zoning
| Date |
Description |
Inspector |
Results |
Comments |
| 02/16/2024 |
COT - RSBU - Excavation/Rebar/Zoning |
|
Re-inspection required |
2/16/24: rebar must maintain a 3" clearance from earth all around (making contact throughout), STHD 10 missing at garage (plan calls for 4 only 3 installed), holdowns must be tied to reinforcement, post footing detail calls for 30" wide square by 20" height at both post footings, footing at interior bearing wall not per plan, casita not complete missing reinforcement on west wall. |
| 02/22/2024 |
COT - RSBU - Excavation/Rebar/Zoning |
|
Passed |
|