Inspection Status: Passed
Inspection History: BULD - Electrical Clearance
| Date |
Description |
Inspector |
Results |
Comments |
| 02/02/2024 |
BULD - Electrical Clearance |
|
Passed |
Duplicate inspection. Passed on 9/11/23 by RM. |
| 09/07/2023 |
BULD - Electrical Clearance |
|
Re-inspection required |
9/7/23: missing address labeling at meter pack main panel, no grounding means at panel, breakers at meters missing, torque spec sheet needed |
| 09/11/2023 |
BULD - Electrical Clearance |
|
Passed |
9/11/23: Feeder wires have been properly torqued. Mast, weather head, meter box, ground wire, ground rods, and wiring are installed. okay to energize meter |