Inspection Status: Not Ready

Inspection History: COT - RSEL - Electrical Final 

Permit Number - TC-RES-0823-07124

Inspection Description - COT - RSEL - Electrical Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
07/30/2025 COT - RSEL - Electrical Final  Not Ready 7.30.25
Could not access building, left message and waited. Call back in for another date
08/01/2025 COT - RSEL - Electrical Final  Re-inspection required 8.1.25
Dining room circuit at main panel trips wine fridge circuit
Panel schedule incomplete
T stat required by city inclusive home to be no higher than 48"
GFCI required in laundry room
Pool barrier (alarms at all doors that access pool area, self closing gate) not present
Exterior pipes need insulation
Damaged stucco and dry rot above main panel
Circuits at panel at interior bedroom all exposed by cut out Sheetrock
Penetrations at exposed wire area need to be sealed
Cs16 protective plate required at exposed circuits, take photograph before covering with Sheetrock
Improper transitions pvc to pvc and pvc to abs at kitchen island, green glue not permitted for these transitions, male to female threaded adapters or approved adapter fitting required per code. Ref p303.14.4
NOT READY - STOPPED INSPECTION ADDITIONAL ITEMS MAY BE ADDED
(Note to inspector: rewalk entire home and exterior)
08/22/2025 COT - RSEL - Electrical Final  Re-inspection required 8.22.2025
Paver or landing required in ADU to side yard, hot water heater room in ADU not wired and disconnect not wired. Rear storage room in ADU needs to be GFCI. AC unit at main house over-amped manufacture label is 40A and disconnect requires Noalox compound for aluminum wire. Doors to ADU from garage need to be self-closings. Oven in ADU needs to be braced to prevent tilting. Missing receptacle in garage. Insulate exposed copper lines in hot water units.
10/15/2025 COT - RSEL - Electrical Final  Passed