Parcel: 11707229A

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-RES-0823-07092

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
06/09/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 6/9/25: Missing anchor bolt in kitchen/living room (12" from edge of sill plate), tighten anchor bolt at kitchen/living room south wall (marked with red marker), Hangers are not properly fastened at trusses (fasteners required throughout), fastener spacing at exterior sheathing not per plan, fasteners shall be no closer than 3/8" from edge's and shall penetrate no more than 1/8".
06/11/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed