Inspection Status: Partial Pass
Inspection History: COT - RSPL - Rough Soil
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/11/2026 | COT - RSPL - Rough Soil | Partial Pass | ||
| 08/26/2026 | COT - RSPL - Rough Soil | Not Ready | Not ready. Provide a minimum of 18" of stand pipe at laundry room along with trap. Provide San t at laundry room and ensure there is a minimum of 4" clearance between each trap weir. Ensure laundry pipe is a minimum of 2". Bathroom underground not approved. Provide a vent through roof for bathroom group. Provide a minimum 2" pipe for shower. Fitting coming from shower is running in the wrong direction. Ensure at next inspection abs is under pressure. 8/26/2026 |
|
| 09/03/2026 | COT - RSPL - Rough Soil | Partial Pass | ||
| 09/11/2026 | COT - RSPL - Rough Soil | Passed |