Inspection Status: Re-inspection required

Inspection History: Pool/Spa - Plumbing

Date Description Inspector Results Comments
08/19/2026 Pool/Spa - Plumbing Re-inspection required 1. Water lines are not under test
2. Galvanized Water risers for hose bibs must not be in contact with earth, needs minimum of 3-6 inches separation.
3. Too much rocks in the trenches, provide shading for a firm bed before backfilling with rocky soil.
4. Separate gas line and electric in trench by 6-12".
08/25/2026 Pool/Spa - Plumbing Passed 8-25-26 plumbing per approved plans OK to backfill shading is required