Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
08/27/2026 COT - RSME - Mechanical Final  Re-inspection required 8-27-26: fix tear to flex in attic, install lockable caps at condenser, provide a 90 degree elbow at condensation line located on west exterior wall, identify HVAC breaker and make corrections if needed- max breaker to unit is 45, secure HVAC line set within 12" of disconnect.
09/14/2026 COT - RSME - Mechanical Final  Passed 09/14/2026
Corrections made to prior inspection.